Pure Lead Plus
Valve Regulated Lead Acid Battery
Designed for UPS Standby Power Applications
Valve Regulated Lead Acid Battery
Designed for UPS Standby Power Applications
| Operating Temperature Range with temperature compensation | Discharge: -40°F (-40°C) to +160°F (71°C) Charge: -10°F (-23°C) to +140°F (60°C) |
|---|---|
| Nominal Operating Temperature Range | +74°F (23°C) to +80°F (27°C) |
| Recommended Maximum Charging Current Limit | C/5 amperes @ 20hr rate |
| Float Charging Voltage | 13.65 ± 0.15 VDC average per 12V unit |
| Maximum AC Ripple (Charger) | 0.5% RMS or 1.5% P-P of float charge voltage recommended for best results. Max voltage allowed = 1.4% RMS (4% P-P) Max current allowed = C/20 A RMS |
| Self Discharge | Battery can be stored up to 4 months at 77°F (25°C) before a freshening charge is required. Batteries stored at temperatures greater than 77°F (25°C) will require recharge sooner than batteries stored at lower temperatures. See C&D brochure 41-7272, Self-Discharge and Inventory Control for details. |
| Equalize charge and cycle service voltage | 14.40 to 14.80 VDC average per 12V unit @ 77°F (25°C) |
| Model | Cell per Unit | Maximum Discharge Current (Amps) | IEC Short Current (Amps) | IEC Resistance (mΩ) |
|---|---|---|---|---|
| UPS 12-3300 PLP | 6 | 800 | 2381 | 5.29 |
| UPS 12-3800 PLP | 6 | 800 | 2734 | 4.65 |
| UPS 12-4000 PLP | 6 | 800 | 3199 | 4.06 |
| UPS 12-4700 PLP | 6 | 800 | 3350 | 3.77 |
| UPS 12-4800 PLP | 6 | 800 | 3160 | 3.96 |
| UPS 12-5400 PLP | 6 | 800 | 3613 | 3.48 |
| UPS 12-6300 PLP | 6 | 800 | 4146 | 2.99 |
| UPS 12-4200F PLP | 6 | 800 | 2864 | 4.40 |
| UPS 12-6200F PLP | 6 | 800 | 3698 | 3.40 |
| UPS 12-6800F PLP | 6 | 900 | 4400 | 2.80 |
| UPS 12-8000F PLP | 6 | 1200 | 5376 | 2.31 |
| UPS 12-9200F PLP | 6 | 1200 | 5543 | 2.28 |