MRXF Series
Valve Regulated Lead Acid (VRLA) Battery Series
Design For UPS Standby Power Applications
Valve Regulated Lead Acid (VRLA) Battery Series
Design For UPS Standby Power Applications
| Operating Temperature Range with temperature compensation | Discharge: -40°F (-40°C) to +J 60°F (7 J°C) Charge: -10°F (-23°C) to +140°F (60°C) |
|---|---|
| Nominal Operating Temperature Range | +74°F (23°C) to +80°F (27°C) |
| Recommended Maximum Charging Current Limit | C/5 amperes @ 20hr rate |
| Float Charging Voltage | 13.5 to 13.8 VDC average per 12V unit @ 77°F (25°C)(Recommendation:13.65V per unit) |
| Maximum AC Ripple (Charger) | 0.5% RMS or 1.5% P-P of float charge voltage recommended for best results. Max voltage allowed = 1.4% RMS (4% P-P) Max current allowed = C/20 |
| Self Discharge | Battery can be stored up to 4 months at 77°F (25°C) before a freshening charge is required. Batteries stored at temperatures greater than 77°F (25°C) will require recharge sooner than batteries stored at lower temperatures. See C&D brochure 41-7272, Self-Discharge and Inventory Control for details. |
| Terminal: Inserted - Inter-unit connector provided | Threaded copper alloy insert terminal to accept: M6 bolt (UPS 12-4J 0 MRXF) M8 bolt (UPS J2-6J 5 MRXF, UPS 12-700 MRXF, UPS 12-830 MRXF, UPS J2-J 000 MRXF) |
| Terminal Hardware mitial Torque | 110 in.-lbs (12.4 N-m) for UPS 1 2-410 MRXF , UPS 12-515 MRXF 160 in.-lbs. (18 N-m) for UPS 1 2-615 MRXF, UPS 1 2-700 MRXF, UPS 1 2-830 MRXF, UPS 1 2-1000 MRXF |
| Model | Cell per Unit | Maximum Discharge Current (Amps) | IEC Short Current (Amps) | IEC Resistance (mΩ) |
|---|---|---|---|---|
| UPS 12-410 MRXF | - | - | 2860 | 4.4 |
| UPS 12-515 MRXF | - | - | 3500 | 3.6 |
| UPS 12-ó1S MRXF | - | - | 3700 | 3.4 |
| UPS 12-700 MRXF | - | - | 4400 | 2.8 |
| UPS 12-830 MRXF | - | - | 5376 | 2.31 |
| UPS 12-1000 MRXF | - | - | 5S40 | 2.3 |