MRX Series
Valve Regulated Lead Acid Battery
Designed for UPS Standby Power Applications
Valve Regulated Lead Acid Battery
Designed for UPS Standby Power Applications
| Operating Temperature Range with temperature compensation | Discharge: -40°F (- 40 deg * C) to +160°F ( (71 deg * C) | Charge: -10°F (-23°C) to +140°F (60°C) |
|---|---|
| Nominal Operating Temperature Range | underline + 74 ^ prime prime F (23 deg * C) to +80°F (27°C) |
| Recommended Maximum Charging Current Limit | C/5 amperes 20hr rate |
| Float Charging Voltage | 13.65±0.15VDC per unit at 25 deg * C Recommendation: 13.65V per unit) |
| Maximum AC Ripple (Charger) | 0.5% RMS or 1.5% P-P of float charge voltage recommended for best results. Max voltage allowed = 1.4% RMS (4% P-P), Max current allowed = C/20 A RMS |
| Self Discharge | Battery can be stored up to 4 months at 77 deg * F (25 deg * C) before a freshening charge is required. Batteries stored at temperatures greater than (25 deg * C) will require recharge sooner than batteries stored at lower temperatures. See C&D brochure 41-7272, Self-Discharge and Inventory Control for details. |
| Equalize charge and cycle service voltage | 14,40 to 14.80 VDC average per 12V unit @ 77°F (25 deg * C) |
| Accessories (Optional) | Inter unit connectors, racks and cabinet systems are available. |