ACE Reliable Power Solution

Pure Lead Plus

Valve Regulated Lead Acid Battery
Designed for UPS Standby Power Applications

  • Features & Benefits
  • Applications
  • Specifications
  • 15 year design life @25℃
  • Eurobat classification: Long life
  • Pure Lead Paste for long life, extreme high rate and stable performance
  • 5 years Warranty
  • Absorbent Glass Mat (AGM) technology for efficient gas recombination of up to 99% and freedom from electrolyte maintenance
  • C&D’s Long Life Alloy having very low calcium levels in the industry -minimizing grid growth, reducing gassing, and extending battery life
  • UL Recognized Flame-arresting vents in each cell for safety and long life
  • Designed with the same recombination, thermal runaway prevention, gassing and flame retardant characteristics of the Bellcore 4228 compliant Dynasty Telecom products
  • Flame retardant polypropylene case and cover compliant with UL94 V-0
  • C&D’s plate processing technology for high active materials utilization- result in high energy density and low flow currents
  • Thermally welded and Helium leak tested case-to-cover bond to ensure a robust leak proof seal
  • Not restricted for air transport -Complies with IATA/ICAO Special Provisions A67
  • Not restricted for surface transport - Classified as non-hazardous material as related to DOT-CFR Title 49 parts171- 189
  • Not restricted for water transport - Classified as non-hazardous material per IMDG Amendment 27.
  • Data Centers
  • Network Operation Centers
  • Industrial Process Control Facilities
  • Internet Housing Sites
  • Semiconductor Manufacturing
  • Banks and Financial Markets
  • Power Generation Plants
  • Hospital and Testing Laboratories
  • Emergency Response Center
Operating Temperature Range with temperature compensation Discharge: -40°F (-40°C) to +160°F (71°C) Charge: -10°F (-23°C) to +140°F (60°C)
Nominal Operating Temperature Range +74°F (23°C) to +80°F (27°C)
Recommended Maximum Charging Current Limit C/5 amperes @ 20hr rate
Float Charging Voltage 13.65 ± 0.15 VDC average per 12V unit
Maximum AC Ripple (Charger) 0.5% RMS or 1.5% P-P of float charge voltage recommended for best results. Max voltage allowed = 1.4% RMS (4% P-P) Max current allowed = C/20 A RMS
Self Discharge Battery can be stored up to 4 months at 77°F (25°C) before a freshening charge is required. Batteries stored at temperatures greater than 77°F (25°C) will require recharge sooner than batteries stored at lower temperatures. See C&D brochure 41-7272, Self-Discharge and Inventory Control for details.
Equalize charge and cycle service voltage 14.40 to 14.80 VDC average per 12V unit @ 77°F (25°C)
Model Cell per Unit Maximum Discharge Current (Amps) IEC Short Current (Amps) IEC Resistance (mΩ)
UPS 12-3300 PLP 6 800 2381 5.29
UPS 12-3800 PLP 6 800 2734 4.65
UPS 12-4000 PLP 6 800 3199 4.06
UPS 12-4700 PLP 6 800 3350 3.77
UPS 12-4800 PLP 6 800 3160 3.96
UPS 12-5400 PLP 6 800 3613 3.48
UPS 12-6300 PLP 6 800 4146 2.99
UPS 12-4200F PLP 6 800 2864 4.40
UPS 12-6200F PLP 6 800 3698 3.40
UPS 12-6800F PLP 6 900 4400 2.80
UPS 12-8000F PLP 6 1200 5376 2.31
UPS 12-9200F PLP 6 1200 5543 2.28